Input & Output |
Input Voltage Range |
220V±15% |
Input Frequency Range |
47~63Hz |
Output Voltage Range |
0~rated input voltage |
Output Frequency Range |
0~400Hz |
Protection Functions |
over voltage,over current,under voltage,overload,overload,overheating,electronic thermal,ground fault |
I/O Features |
Programmable Digital Input |
4 input terminal |
Programmable Analog Input |
AI2:0~10 or 0~20mA input |
Programmable Open Collector Output |
1 output terminal |
Relay Output |
1 output terminal |
Analog Output |
1 output terminal,whose output scope can be 0/4~20 mA or 0~10 V, as chosen. |
Main Control Function |
Control Mode |
V/F control |
Overload Capacity |
60s with 150% of rated current, 10s with 180% of rated current. |
Carrier Frequency |
0.5k~15.0kHz |
Function Features |
Frequency reference source |
keypad, analog input, multi-stage speed, simple PLC |
Simple PLC, Multi-Steps Speed Control Function |
8 stages speed can be set. |
Traverse Control Function |
None-Stop when instantaneous power off |
QUICK/JOG Key |
User defined shortcut key can be realized |
Automatic Voltage Regulation Function (AVR) |
Automatically keep the output voltage stable when input voltage fluctuating |
Up to 25 fault protections |
Protect from over current, over voltage, under voltage, over temperature, phase failure, over load etc. |